Structural Features
● The cabinet adopts an armored structure, and various functional compartments are separated by metal plates, achieving an enclosure protection level of IP4X.
● The cabinet structure is assembled using aluminum-zinc-plated sheets processed through multiple folds, providing sufficient strength and rigidity.
● The circuit breaker handcart adopts a center-mounted arrangement, ensuring good interchangeability. It possesses a simple and reliable "five prevention" function.
● The cable compartment provides ample space, allowing the connection of multiple cables and facilitating convenient installation and maintenance.
Operating Environment Requirements
● Air Temperature: Maximum +40°C, Minimum -15°C.
● Relative Humidity:
Daily average relative humidity: ≤95%
Daily average water vapor pressure not exceeding 2.2kPa
Monthly average relative humidity: ≤90%
Monthly average water vapor pressure not exceeding 1.8kPa.
● Seismic Intensity: Not exceed 8 degrees.
● The surrounding air should not be significantly polluted by corrosive or combustible gases, water vapor, etc.
● No severe vibration.
● When used beyond the normal conditions specified in GB3906, it should be negotiated between the user and the manufacturer.
|
Parameters Name |
Unit |
Content |
|
Standards |
/ |
IEC60298、GB3906 |
|
Protection Level |
/ |
IP4X for enclosure protection level IP2X when compartment and circuit breaker room doors are open |
|
Rated Voltage |
kV |
12 |
|
1 min Power Frequency Withstand Voltage |
kV |
Betwee phases and to earth : 42; Across contact:48 |
|
Lightning Impulse Withstand Voltage |
kV |
Betwee phases and to earth: 75; Across contact: 85 |
|
Rated Current |
A |
630/1250/1600/2000/2500/3150/4000 |
|
Rated Short-Circuit Breaking Current |
kA |
20/25/31.5/40 |
|
Rated Short-Circuit Closing Current |
kA |
50/63/80/100 |
|
Rated Steady-State Current |
kA |
50/63/80/100 |
|
Rated Thermal Stability Current for 4 Seconds |
kA |
50/63/80/100 |
|
Dimensions (Width x Depth x Height) |
cm |
800(1000) x 1500(1660) x 2300 |